Doors.NET Reference Manual
- 376 -
6. Give both Areas a new name - One for door 1, the other for door 2, for example:
7. Highlight the first Area so that the properties can be seen on the right. Set Enable
Airlock and Enforce Airlock One Door to Yes.
8. Then do the same for the second Area.
9. Highlight the reader in the hardware tree that relates to door 1 and in the reader
properties locate the Anti-Passback settings.
l Anti-Passback Mode - must be set to Hard
l Enter Area - must be set to Door 1 (or the name assigned to the first area)
l Exit Area must be set to Door 2 (or the name assigned to the second area)
Vedere la pagina 375